Thermal stratification characteristics during simultaneous charging and discharging for different storage tank geometries with immersed discharging coil

Publication Details
Co-authored with Hitesh Khurana and Sandip K. Saha. Applied Thermal Engineering Vol, 225: 120235
Publication Type
Publication Category
Blurb

dictate the efficacy of low-to-medium temperature hot water applications. This study uses a three-dimensional
numerical model to investigate the thermal characteristics of three storage configurations for simultaneous
charging and discharging. The same tank volume and height, as well as the same coil tube dimensions, are
considered for three different configurations - cylindrical tank with a helical discharging coil, as well as circular
truncated cone-shaped and paraboloidal tanks with conical discharging coils. The discharging flow rate is varied
for a deeper understanding of the realistic interplay between energy demand and supply. Results obtained for the
cylindrical tank are found to have good agreement with the observations from the in-house experiments. The
energy stored, discharging coil outlet temperature, and the extent of thermal stratification decrease with
increasing coil flow rate, whilst discharging efficiency and primary thermocline thickness increase. The paraboloidal
tank equipped with a conical discharging coil exhibited the highest cumulative energy stored (8821 kJ)
just before the commencement of dynamic dual operation, owing to the minimal thermal losses attributable to
the lowest surface-area-to-volume ratio. Thermocline thickness is found to expand with time for all the cases, and
the highest thermocline thickness expansion rate of 0.208 mm/s is found for the cylindrical tank indicating a
higher degree of energy degradation. The peak values for the cumulative energy discharged (9788 kJ), and
average discharging efficiency (0.36) occurred for the paraboloidal tank with the conical discharging coil
configuration. Based on the detailed analyses, the paraboloidal storage tank configuration is found to exhibit
better system reliability and energy management, leading to more efficient heat dispatch controllability due to
the enhanced energy harnessing features.

Publication date( Day/Month/Year)
Author of the Publication